- yjv22-1kv-3*50+2*25铠装电力电缆
详细信息
品牌:华强牌 型号:yjv22-1kv-3*50+2*25 线芯材质:铜丝 电压等级:中.低压电力电缆(35千伏及以下) 绝缘材料:塑料绝缘电力电缆 芯数:5 护套材质:聚氯乙烯 电线最大外径:40 mm 绝缘厚度:1.7 mm 标称截面:50 mm2 用途:电力电缆
本产品按GB/T 12706-2002《额定电压1KV(Um=1.2KV) 到35Kv(Um=40.6KV)挤包绝缘电力电缆及附件》标准生产,同时还可根据用户需要按国际电工委员会推荐IEC标准、英国标准、德国标准及美国标准生产。
The product is manufactured according to the standards of GB/T 12706-2002。At the same time ,it can also be manufactured according to IEC, BS, DIN and AEIC upon request.
yjv22-1kv-3*50+2*25铠装电力电缆适用范围 Application
本产品适用于工频额定电压0.6/1kV及以下配电网或工业装置中固定敷设之用。
The product is suitable for power distribution lines or fixed installation with rated power- frequency voltage up to and including 0.6/1kV.
yjv22-1kv-3*50+2*25铠装电力电缆使用特性 Operating Characteristics
工频额定Uo/U为0.6/1kV。
Rated power-frequency voltage Uo/U is 0.6/1kV.
电缆导体允许长期*高工作温度为90℃。
Max. permissible continuous operating temperature of conductor is 90℃.
短路时(*长持续时间不超过5s)电缆导体的*高温度不超过250℃。
Max. temperature of conductor during short circuit (5s maximum duration ) shall not exceed 250℃.
电缆敷设时环境温度应不低于0℃。
The ambient temperature under installation should not below 0℃.
电缆弯曲半径:单芯电缆不小于电缆外径20倍;三芯电缆不小于电缆外径15倍。
The bending radius of a single-core cable: not less than 20 times of cable’s OD
The bending radius of a three-core cable: not less than 15 times of cable’s.OD
电缆敷设运行条件 Installation operating condition of cable
在空气中的敷设 In Air
1.单芯电缆平行敷设时中心距离:185mm2及以下为电缆直径的2倍;240mm2及以上为90mm。
If the single-core cables are paralleled laid , the distance between the cable center is 2 times diameter of the cable for cross-section of conductor≤185 mm2 and 90mm for cross-section of conductor ≥240 mm2.
周围环境空气温度:40℃
Ambient air temperature: 40℃
导体的长期允许*高工作温度:90℃
Max. continuous operating temperature of conductor:90℃
不同环境温度下的载流量修正系数:
Correction factor of current rating under different air temperature:
Ambient temperature20℃
25℃
30℃
35℃
40℃
45℃
50℃
55℃
Correction factor
1.23
1.17
1.12
1.06
1.00
0.94
0.87
0.81
直埋敷设 Direct in the ground
单芯电缆不接触敷设时电缆中心距离为电缆直径的2倍。
If he single-core cables are installed separately , the distance between the cable’s center is 2 times diameter of the cable.
土壤温度:25℃
Soil temperature: 25℃
导体的长期允许*高工作温度: 90℃
Max. continuous operating temperature of conductor: 90℃
4. 土壤热阻系数:1.0k.m/w ]
Soil thermal resistivity:1.0k.m/w
5. 直埋深度:0.7m
Depth of laying : 0.7 m.
不同土壤温度下的载流量修正系数:
Correction factor of current rating under different soil temperature:
Soil temperature10℃
15℃
20℃
25℃
30℃
35℃
Correction factor
1.11
1.07
1.04
1.00
0.96
0.92